Time series
Before a power flow can be run, every load, generator and storage unit needs an active- and reactive-power time series. eDisGo offers several ways to set them.
Note
Set the time index before setting any time series — either via the
timeindex argument of the EDisGo constructor or with
set_timeindex(). And remember the
ordering rules: reactive power is always set last.
Reference year
All time series of an EDisGo object are indexed in one calendar year, the
reference year. It defaults to 2011, the weather year of the model data, and is set
in section timeindex of config_timeseries.cfg (see config_timeseries):
[timeindex]
reference_year = 2011
It can also be changed on an existing object before any time series is set:
edisgo.config["timeindex"]["reference_year"] = 2013
A time index or time series in another year, e.g. one passed to
set_timeindex() or to an import, is relabelled to the
reference year with a warning. The data is only relabelled, not changed: each time
step keeps its date and time, so 1 March stays 1 March. The scenario of a database
import only selects which data is loaded, it does not set the year.
29 February is always left out, also if the reference year is a leap year, so a year
always has 365 days. A time index across the year boundary, e.g. from 31 December to
1 January, raises a ValueError. The worst-case time index starting
1970-01-01 (see Worst-case) is not changed.
The relabelling is done by the import and set_* methods, e.g.
set_time_series_manual(),
set_cop() or
from_etrago(). Data assigned
directly to an attribute, e.g. edisgo.dsm.p_min, edisgo.heat_pump.cop_df or an
attribute of edisgo.overlying_grid, or passed to
set_active_power_manual(), is stored as
given and must already be indexed in the reference year.
Active power
There are five ways to set active-power series:
Manual
Provide your own series with set_time_series_manual().
Pass a pandas DataFrame per component category, indexed by the time index and
with one column per component:
import pandas as pd
edisgo.set_time_series_manual(
loads_p=pd.DataFrame(
{"Load_1": [0.5, 0.6]}, index=edisgo.timeseries.timeindex
),
)
The arguments are generators_p, loads_p, storage_units_p for active power
and generators_q, loads_q, storage_units_q for reactive power. Values are
in MW (active) and Mvar (reactive); the DataFrame index must contain the time
index set on the object.
Worst-case
Set feed-in and load for the two classic grid-planning situations — heavy load
(load_case) and reverse power flow (feed-in_case) — using simultaneity
factors from the configuration files. This sets both active and reactive power
(reactive power with fixed cos φ from the config), so no separate reactive-power step
is needed afterwards.
edisgo.set_time_series_worst_case_analysis()
A fictitious time index starting 1970-01-01 00:00 is set automatically (PyPSA needs
a time index). Each case is set up once for the MV and once for the LV level, so there
are four time steps in total; edisgo.timeseries.timeindex_worst_cases tells you
which time step maps to which case. Note that this overwrites any previously set
(non-worst-case) time series. The definition of load and feed-in case is explained in
Load case and feed-in case.
Predefined
Set series by component type, either from your own data or from public sources. Each component group has its own argument; a call with no arguments sets no time series at all, so you have to specify the desired source explicitly, e.g.:
edisgo.set_time_series_active_power_predefined(
fluctuating_generators_ts="oedb",
conventional_loads_ts="demandlib",
)
Fluctuating generators (
fluctuating_generators_ts) — wind and solar feed-in from theoedb(OpenEnergy DataBase), or your own normalised profiles per technology (optionally per technology and weather cell) passed as aDataFrame.Dispatchable generators (
dispatchable_generators_ts) — your own normalised profiles per technology, where a column"other"acts as catch-all for all technologies not listed explicitly.Conventional loads (
conventional_loads_ts) — standard load profiles per sector viademandlib, scenario-specific per-building profiles from theoedb(requires anengineand ascenario), or your own sector profiles as aDataFrame(see Data sources).Charging points (
charging_points_ts) — pass normalised profiles per use case (there is nooedbsource for charging points, and only the use cases you supply are set). If you omit it, charging points — includingpublicones — are left without a series. To set them automatically instead, useapply_charging_strategy()(see Charging strategies (heuristic)), which covers all charging points (public/hpccharged “dumb”).
See set_time_series_active_power_predefined() for all
options. If no time index has been set, a full-year index in the reference year is
set automatically.
Optimised
Optimise the operation of flexibilities (EV charging, heat pumps with thermal
storage, DSM, storage) with a multi-period optimal power flow, so that grid
expansion is minimised. This is pm_optimize(); it is
documented in detail in Multi-period optimal power flow.
Heuristic
Apply rule-based operation strategies. For electric vehicles use a charging strategy:
edisgo.apply_charging_strategy(strategy="dumb") # "dumb", "reduced" or "residual"
For heat pumps, the (currently uncontrolled) operating strategy serves the heat demand directly from the heat pump:
edisgo.apply_heat_pump_operating_strategy()
See Heat pumps for details.
Reactive power
Two options exist for setting reactive power explicitly (note that
set_time_series_worst_case_analysis() already sets
fixed-cos-φ reactive power itself, so neither is needed after a worst-case setup).
Manual
Provide your own series, as for active power above.
Fixed cos φ
Derive reactive power from active power with a fixed power factor:
edisgo.set_time_series_reactive_power_control()
By default ("default") the power factors and inductive/capacitive mode are taken
from the configuration files. You can override them per component group via the
generators_parametrisation / loads_parametrisation /
storage_units_parametrisation arguments (a DataFrame with columns
components, mode and power_factor), or set a group to None to leave it
untouched — all three default to "default". Make sure the active-power series are
set first. The sign conventions and the formula Q = P · tan(arccos(cos φ)) are
explained in Reactive power.
Scaling existing series
Already-set series can be scaled up or down (e.g. for a sensitivity study) with
scale_timeseries(), applied in place to all
generators, loads and storage units:
edisgo.timeseries.scale_timeseries(p_scaling_factor=1.1, q_scaling_factor=1.0)